| HBA-YSAD2兩線制系列電流變送器的初、次級之間是絕緣的,可用于測量交流電流。 (HBA-YSAD2 Series Current transducer of two wire system between primary and secondary is insulated, can be used for the measurement of AC current) | 電氣參數(shù)(Electrical characteristics) | | | 型號 Type | HBA5-YSAD2 | HBA10-YSAD2 | HBA30-YSAD2 | HBA50-YSAD2 | | | Ipn | 額定輸入電流(AC) Rated input | 5 | 10 | 30 | 50 | A | | Ipm | 測量電流范圍(AC) Measuring range | 6 | 12 | 36 | 60 | A | | Rm | 測量電阻 Measuring resistance | 0-400 | Ω | | Iout | 輸出電流 Rated output current | 4~20 | mA | | Io | 零電流失調(diào) Zero offset current | <4±0.1 | mA | | Vc | 供電電壓Supply voltage | +24±5% | V | | Ic | 靜態(tài)功耗 Current consumption | ≤25+Iout | mA | | Iot | 零點溫漂 Thermal drift of Io | ≤±0.005 | mA/℃ | | F | 帶寬Frequency bandwidth(-3dB) | 40~1000 | Hz | | εG | 精度 Accuracy | 0.5 | % | | εL | 線性度 Linearity | 0.5 | % | | Tr | 響應(yīng)時間 Response time | ≤200 | mS | | Vd | 絕緣電壓 Insulation voltage | 2.5 | KV | | Ta | 工作溫度 Ambient operating temperature | -40~+85 | ℃ | | Ts | 儲存溫度 Ambient storage temperature | -40~+105 | ℃ | | M | 重量 mass | 90 | g | | | 標(biāo)準(zhǔn)Standards | EN50178/IEC61010-1/UL94-Vo/ROHS | | 使用說明Remarks 1、 應(yīng)用:通訊電源、不間斷電源UPS、斬波器、電化學(xué)、整流、電源監(jiān)測、電焊機(jī)、變頻、開關(guān)電源、電池監(jiān)測、電動機(jī)監(jiān)測等領(lǐng)域。Application: communication power supply, uninterruptible power supply UPS chopper, electrochemical, rectifier, power monitoring, welding machines, inverter, switching power supply, battery monitoring, motor monitoring fields. 2、傳感器的輸出幅度可根據(jù)用戶需要進(jìn)行適當(dāng)調(diào)節(jié)。The amplitude of the output of the sensor can be appropriately adjusted according to user needs. 3、可按用戶需求定制不同額定輸入電流和輸出電壓的傳感器。Custom different rated input current and the output voltage of the sensor. 4、當(dāng)待測電流從變送器穿過,即可在輸出端測得電流大小。(注意:錯誤的接線可能導(dǎo)致變送器損壞)When the current to be measured is across from the transmitter can be measured at the output current size. (Note: incorrect wiring may cause transmitter damage) 下載詳細(xì)資料 HBA-YSAD2.pdf |